MCS 106452 Digital Synchroscope Meter
- Product Details
- Company Profile
MCS 106452 Digital Synchroscope Meter
Synchronization Meter is an instrument in the electrical instrumentation industry to measure and display the synchronization status between devices. It helps users determine whether there is a synchronization problem between devices by detecting parameters such as current, voltage, and frequency. The instrument is equipped with an intuitive display, which can display the synchronization status of the device in real time, and provide corresponding alarm functions, so that users can take timely measures to solve synchronization problems.
Synchronization Meter has the characteristics of high precision, ease of use, and strong reliability, and is widely used in power systems, industrial automation, and new energy fields.
Features
Color touch screen for easy navigation
Easy to read display with graphical analysis
Durable steel casing for longer life span
Potential free relay contact
Applications
For data synchronization between databases
Data synchronization across different platforms
Synchronize the data generated in real time to the data analysis platform
Real-time analysis and report generation
Data backup and recovery
Synchronize data between different applications for data sharing and process integration
Synchronize data between different cloud service providers
Achieving Data Consistency in Multi-Cloud Environments
Specification
Accuracy | |
Phase angle difference (?θ) | ±2° |
Voltage difference (?v) | ±1% of nominal value |
Frequency difference (?f) | ±0.15 Hz |
Reference conditions for accuracy | |
Ambient temperature | 23°C ±2°C |
Input voltage | Rated voltage ±2% |
Input voltage | |
Nominal input voltage (ac rms) | 100-500 V |
Max continuous input voltage | 600 V |
Overload withstand | 2x nominal voltage for 1 second, repeated 10 times at 10 second intervals |
Frequency measuring range | 45-65 Hz |
Nominal input voltage burden | < 0.2 VA (approx.) |
Auxiliary supply | |
Auxiliary voltage and burden | 100-500 V AC/DC, 45-65 Hz, 8 VA |
Display update rate | |
Response time to step input | 1 second (approx.) |
Applicable standards | |
Safety | IEC 61010-1-2010, permanently connected use |
Ip for water and dust | IP 54 (front) IEC60529 |
Pollution degree | 2 |
Installation category | III |
Isolation between running and incoming circuits | 2 kV RMS for 1 minute |
Environmental conditions and other specs | |
Operating temperature | -10 to +55°C |
Storage temperature | -20 to +65°C |
Relative humidity | 0… 95% non-condensing |
Warm-up time | Minimum 3 minute |
Shock | 15g in 3 planes |
Vibration | 10…150….10 Hz, 0.075mm amplitude |
Temperature coefficient | 0.05%/C |