APPLICATION 

This series of thermal relay can be used in the circuit of 50Hz or 60Hz,rated insulation

voltage 660V,rated current 0.1-96A for protecting the phase break when the electric motor is

overload. The relay has different mechanism and temperature compensation & can be

plugged in LC1-D series AC contactor.It is the most advanced thermal relay in the nineties in the world.

CHARACTERISTICE 

      A.Fundamental parameter of the main circuit

(a).Rated insulation voltage 660V.
(b).Rated working current 25,36,93A separately.
(c).The regulator seal of rated setting current and setting.
(d).Current of the thermal component(see list 1)

      B.Auxiliary Circuit
(a).There is one pair of NO/ and N/C contact with electric insulation.
(b).Rated insulation voltage 500V.
(c).Rated frequency 50-60Hz.
(d).Use group, rated working voltage ,appoint thermal current and rated  current.

Motion Characteristic: Three-phase Balance Motion Time

 

NoTimes of the setting currentMotion timeStart conditionAmbient temperature
11.05>2hCold state20±5oC
21.2<2hHeat state(Following the No.1 test)
31.5<4min
47.210A2s< Tp≤10s≤63ACold state
104s< Tp≤10s>63A

Phase-losing Motion Characteristic

NoTimes of the setting currentMotion timeStart conditionAmbienttemperature
Any two phasesAnother phase
11.00.9>2hCold state20±5oC
21.150<2hHeat state(Following the No.1 test)