KNLE2-63 Earth leakage circuit breaker
- Product Details
- Company Profile
KNLE2-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A.
KNLE2-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
KNLE2-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as well as infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.
Frame class | 63A |
Rated working voltage | 240V |
Rated frequency | 50/60Hz |
Rated working current | 6、10、16、20、25、32、40、50、63A |
Rated residual operating current | 0.01、0.03A |
Rated residual un-operating current | 0.005、0.015A |
Sensibility | C Type |
Maximum operating time | I△n t≤0.3s , 5I△n t≤0.04s |
Instant release type | B, C, D |
Rated limiting short-circuit current | 6000A |
Limiting value of un-operating current | 6In |
Poles | 1P+N |
Mechanical life | 8000 |
Electric life | 4000 |
Sequence NO . | Release | Test current I/In | Start state | Tripping time | Expected result |
1 | C | 1.13In | Cold state | t≤1h | Not tripping |
2 | C | 1.45In | Start right after the serial NO . 1 test | t<1h | Tripping |
3 | C | 2.55In | Cold state | 1s<t<60s | Tripping |
4 | C | 5In | Cold state | t≤0.1s | Not Tripping |
5 | C | 10In | Cold state | t<0.1s | Tripping |