KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection
KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection
KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection
KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection
KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection
KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection

KNLN6-63 Residual Current Circuit Breaker with Overcurrent Protection

Manufacturer

  • Product Details
  • Company Profile

KNLN6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A.

    KNLN6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage. 
     KNLN6-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as well as infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1. 

Frame class63A
Rated working voltage240V
Rated frequency50/60Hz
Rated working current2、361016202532405063A
Rated residual operating current0.01、0.030.10.3A
Rated residual un-operating current0.5I△n
SensibilityA&AC Type
Maximum operating timeI△n   t0.3s , 5In   t0.04s
Instant release typeB&C type
Rated limiting short-circuit current10000A
Limiting value of un-operating current6In
Poles1P+N
Mechanical life20000
Electric life4000


Sequence NO .ReleaseTest
current I/In
Start stateTripping timeExpected result
1C1.13InCold statet≤1hNot tripping
2C1.45InStart right after the serial NO . 1 testt<1hTripping
3C2.55InCold state1s<t60sTripping
4C5InCold statet≤0.1sNot Tripping
5C10InCold statet<0.1sTripping


2

Send Inquiry to This Supplier

  • Title
  • From*
  • toCandy
  • Message*
  • Minimum Order Quantity*
  • Unit
  • Verification Code*