MENU
China Chamber of Commerce

Overseas Economic and Trade Zones

Confirm
Cancel
x

Ok
x
Sign into your account
Member ID or Email
Join Free
MP3100 Series 3/1 phase online ups
MP3100 Series 3/1 phase online ups
MP3100 Series 3/1 phase online ups
MP3100 Series 3/1 phase online ups

MP3100 Series 3/1 phase online ups

Member Details

FOSHAN BAYKEE NEW ENERGY TECHNOLOGY INCORPORATED COMPANY

Foshan,Guangdong,China

  • Product Details
  • Company Profile

Input: 380/400/415/200/208/220VAC±25% Output: 380/400/415/200/208/220VAC Frequency: 50Hz , 60Hz Battery Voltage: 360VDC Payment terms: T/T or L/C or Western Union Lead time: 18~20 days Warranty: 2 years

 MP3100 series Brief

MP3100 series on-line intelligent digital UPS agglomerates the essence of Baykee techniques and entirely break through the bottleneck technology in traditional simulation circuit age. It is to adopt the digital control technology, of which the core is high-speed MCU and programmable logic device (CPLD). It brings in the sixth generation low-exhaust and big-power IGBT module and static switch as power devices.It is really the highlights product which was guided by these most advanced technologies all over the world.

High-precision SMD technology to ensure higher precision machine.

digital control technology, fully intelligent digitization.

Barrier free man-machine conversation

Full digital and intelligent

Advanced digital circuit system

Intelligent battery management

Intelligent detection system

ntelligent communication tool

High reliability

The sixth generation IGBT

High speed static switch 

High-precision SMD technology

Perfect protection

User-friendly

humanization great LCD screen

Intuitive LED status indicators

 

MP3100 Series 3/1 phase online ups parameters

 

 

MODEL MP3106K MP3110K MP3115K MP3120K MP3125K MP3103K
Capacity 6kVA 10kVA 15kVA 20kVA 25kVA 30kVA
Power Watt 4.8kW 8kW 12kW 16kW 20kW 24kW
Working Principle Low Freuqency  Transformer Based True On Line-Double Conversion 
RECTIFIER (INPUT)
Phase Three Phase
Input Power Factor Standard > 0.9 ( 6pulse Rectifier+Filter ),  Optional >0.96 ( 12pulse Rectifier+Filter)
Input Voltage Range

220/380VAC (230V/400VAC or 240V/415VAC)±25% 3P+N+PE 

  110V/208V (120V/220V or 277V/480VAC)

Input Frequency 

Range

50Hz±10% / 60Hz±10% (Selectable)
Output Ripple <2%
Soft Start 0~100% 5sec
CHARGING
Charging Mode

Constant current, then constant voltage, and charge with temperature compensation,

 automatic switch Between Equalized charging and Float charging

Float Charging 

Voltage

405VDC

Equalized Charging 

Voltage

432VDC
Temp. Compensated Voltage -3mV/℃/cell
Charging Current 0.1C ( Automatic adjust according to battery capacity)
BATTERY
Type VRLA/AGM/Gel, optional Lithium Battery
Battery Capacity 7~999AH settable ( Choose Battery Capacity according to Back-up Time )
Quantity 30units 12V or 180units 2V batteries (Nominal Voltage 360VDC)
Temperature 20ºC~25ºC (For Maximum Efficiency)
INVERTER (OUTPUT)
Phase Single Phase
Rated Voltage Rated Capacity*0.9
Nominal Voltage 220VAC (230VAC or 240VAC), 1P + N   optional 110V(120V or 277V )

Output Voltage 

Regulated Accuracy

±1 %( Stable load), ±3%( fluctuant load)

Output Frequency

 Range

50Hz 60Hz<±0.5% ( Asynchronous )
Crest Factor > 3:1

Output Total

 Harmonic Distortion (THD)

Pure Sine Wave, Linear Load < 3%, Non-Linear Load<5%

Dynamic 

Characteristics

Instant voltage<±5% ( from 0 to100% ), Instant recover time<10ms

Unbalanced Load

 Voltage

< ± 5%
Overload Capacity At 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S
Inverter Efficiency >93% ( full load )
BYPASS
Phase Single Phase

By-pass Input 

Voltage

220/380VAC (230V/400VAC or 240V/415VAC)  optional 110V(120V or 277V )

By-pass Output 

Voltage

220VAC (230VAC or 240VAC)   optional 110V(120V or 277V )
Transfer Time 0ms( adopt static switch )
PROTECTION FUNCTION
Input Protection Input voltage, frequency over limited protection, Phase fault, Phase lack
Output Protection Over current, short circuit, over voltage, low voltage
Battery Protection Over charge, over-discharge protection

Temperature 

Protection

Environment over temperature protection, inverter over temperature protection

Hardware Fault 

Protection

Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc protection
GENERAL SYSTEM PARAMETERS

Working 

Environment

Temp: -10~40ºC, relative humidity: 30%~90%, Altitude<2000m ( 1% decrease against 100 meters’ rise, max. altitude 4000m )
Cooling Method COMPULSIVE VENTILATION

Communitation 

Interface

RS232/ RS485, optional dry contact, SNMP card ( for remote control via internet )
Parallel Operation Tandem hot backup or parallel connection
Auti-surge Capacity 10/700μS, 5KV;  8/20μS, 20KA
Protection Level IP21
Safety Performance Vin-n Vout-n 2000Vac, creepage<10mA , insulating resistance>2MΩ(500VDC)
Noise (dB) 45~50 50~55 55~58

Dimension 

(W*D*H) mm

450*600*1200
Weight (Kg) 65 168 183 210 241 246

 