CNS Moulded Case Circuit Breaker
- Product Details
- Company Profile
With 30 years experience, we produce quality MCCB with moderate price. Looking for dealer, wholesaler and other type of clients for further cooperation.
Functions and characteristics
Item No. | CNS 800-1600 | |
Number of poles | 3P, 4P | |
Control | Manual | with toggle with direct or extended rotary handle |
Connections | Fixed | front connections |
Plug-in | front connections/rear connections | |
Electrical characteristics as per IEC60947 and EN60947-2 | ||
Rated current(A) In | In | 800, 1000, 1250, 1600 |
Rated insulation voltage(V) | Ui | 800 |
Rated impulse withstand voltage(kV) | Uimp | 8 |
Rated operational voltage(V) | Ue | AC 50/60Hz,690 |
Breaking capacity levels | N H | |
Utilization category | AC | 220/240V 85 85 |
380/415V 50 70 | ||
440V 50 65 | ||
500/525V 40 50 | ||
660/690V 30 42 | ||
Operation performance | Mechanical | 10000 |
Electrical 440V | 5000 | |
Protection Chart C-1 | ||
Overload protection | long-time delay | Ir (In x......) |
Short-circuit protection | short-time delay | Isd (Ir x......) |
Instantaneous | Ii (In x......) | |
Indication and control auxiliaries | ||
Auxiliary switch | ■ | |
MX Shunt coil | ■ | |
MN under-voltage coil | ■ |
Protection
Chart C-1
Protection thresholds and delays are set using the adjustment dials.
Offer standard long time delay setting module.
overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Short-circuit protection
Short-time(rms) and instantaneous protection.
Selection of l't type(ON or OFF)for short-time delay.
Neutral protection
On 3-pole circuit breakers, neutral protection is not possible.
On 4-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5lr (4P 3d +N/2) or neutralprotection at lr (4P 4d).
lndications
Overload indication by alarm LED on the front; the LED goes on when the current exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.