Remote tripping
Shunt Trip (SHT) or Under Voltage Release (UVR/UVRN).
Shunt Trip (SHT)
·This release trips the circuit breaker when the control voltage rises above 0.7 x Un
·Control signals can be of the impulse type (u 20 ms) or maintained.
Under Voltage Release (UVR/UVRN)
This release trips the circuit breaker when the control voltage drops below a tripping threshold
Tripping threshold between 0.35 and 0.7 times the rated voltage
Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage.
Operation
When the circuit breaker has been tripped by an SHT or UVR/UVRN release, it must be reset locally:
SHT or UVR/UVRN tripping takes priority over manual closing
in the presence of a standing trip order, closing of the contacts, even temporary, is not possible.
Circuit breaker tripping by an SHT/UVR/UVRN release meets the requirements of standard IEC 60947-2.