EP-5000-HA-UD/20~35
- Product Details
- Company Profile
MV Station Integrated outdoor inverter, transformer, and Communication& monitoring system
MV Station Integrated outdoor inverter, transformer, and Communication& monitoring system
1500V large capacity centralized grid connection, low initial investment cost
Adapt to various harsh environments such as high temperature, high humidity, high dust, salt spray, etc
Technical Parameters
Input (DC)
Max. PV input voltage | 1500V |
Max. input current | 3260A*2 |
MPP voltage range for nominal power | 900~1300V |
Number of MPPT trackers | 2 |
Number of DC inputs | (14~20)*2 |
Output (AC)
Rated AC output power | 2*2500kVA@50℃ |
Max. AC output power | 2*2875kVA@25℃ |
AC voltage range | 20~35kV |
Rated grid frequency/range | 50 Hz/ 45~55 Hz, 60Hz/ 55~65 Hz |
Output current harmonic (at nominal power) | < 3 % |
DC current injection | < 0.5% In |
Power factor at nominal power/range | >0.99/ 0.8 lagging to 0.8 leading |
Protection
DC input protection | Load break switch+fuse |
AC output protection | Circuit breaker |
AC MV output protection | Circuit breaker |
Overvoltage protection | DC Type II / AC Type II |
Leakage current monitoring | Yes |
Grid monitoring/Ground fault monitoring | Yes/Yes |
Insulation monitoring | Yes |
Overheat protection | Yes |
Night SVG function | Optional |
Anti-PID function | Optional |
Efficiency
Max. efficiency | 99.00% |
EU efficiency | 98.70% |
Transformer
Transformer Rated power | 5000 kVA |
Transformer Max. power | 5750 kVA |
LV / MV Voltage | 0.63-0.63/20~35kV |
Transformer Vector | Dy11y11 |
Transformer cooling type | ONAN (Oil Natural Air Natural) |
General date
Weight | 25t |
Protection level | Inverter:IP65, Others:IP54 |
Auxiliary power supply | Standard:5kVA, Optional: max.40kVA |
Temperature | -30~+60℃ (>50℃ derating) |
Allowed humidity (non condensing) | 0 - 95 % |
Cooling mode | Temperature controlled forced air cooling |
Max.operating altitude | 2000m (standard) / > 2000m (optional) |
Display | LCD |
Communication port | RS485/Ethernet |