SP-60K-L
- Product Details
- Company Profile
DC switch configured for safe operation and maintenance; 3 MPPTs design, overload ratio is up to 1.3
DC switch configured for safe operation and maintenance
3 MPPTs design, overload ratio is up to 1.3
Wireless communication supported to save communication cable cost
Three-level + soft switching technology, ultra-wide MPPT voltage range
Technical Parameters
Input (DC)
Max. PV input voltage | 1100V |
Max. input current | 44A*3 |
Rated input voltage | 620V |
MPP voltage range | 200~1000V |
MPP voltage range for nominal power | 520~850V |
Number of MPPT trackers | 3 |
Max. number of PV strings per MPPT | 4 |
Output (AC)
Rated output power | 66kW@45℃/60kW@50℃ |
Max. output power | 66kW |
Rated grid voltage | 380V/400V |
Grid voltage range | 340~440V |
Max. output current | 100.3A@380V,95.2A@400V |
Rated grid frequency / range | 50Hz/45~55Hz, 60Hz/55~65Hz |
Output current harmonic(at nominal power) | <3% |
Power factor at nominal power / range | >0.99/0.8leading to 0.8lagging |
Protection
DC reverse connection protection | Yes |
Overvoltage protection | DC Type II/AC Type II |
Leakage current protection | Yes |
Grid monitoring | Yes |
Insulation monitoring | Yes |
Anti-island protection | Yes |
Efficiency
Max. efficiency | 98.80% |
EU efficiency | 98.50% |
General date
Isolation method | Transformerless |
Self-consuming in night | <2W |
Protection level | IP65 |
Noise | <60dB |
Temperature | ﹣30℃~+60℃ |
Allowed humidity(non condensing) | 0~100% |
Cooling mode | Temperature controlled forced air cooling |
Max.operating altitude | 4000m (>3000m derating) |
Communication port | Standard:RS485, Optional:WIFI |
Dimensions (W×H×D) | 585×853×295mm |