10-200kVA Three Phase Low Frequency Over Temperature Protection Online UPS Power Supply
- Product Details
- Company Profile
1.IGBT inverter and output isolation transformer 2.Manual maintenance bypass switch 3.Wide input voltage range 4.RS232/RS485/dry contact communication port 5.SNMP adapter (optional) 6.Fully DSP control and high reliability and performance 7.3 phase UPS allow 100% unbalanced load 8.EPO function(optional) 9.7 inches touchable LCD screen(optional)
3B3 10kVA-120kVA
Main feature
1.IGBT inverter and output isolation transformer
2.Manual maintenance bypass switch
3.Wide input voltage range
4.RS232/RS485/dry contact communication port
5.SNMP adapter (optional)
6.Fully DSP control and high reliability and performance
7.3 phase UPS allow 100% unbalanced load
8.EPO function(optional)
9.7 inches touchable LCD screen(optional)
Application
1.Data center
2.Industrial equipment
3.Commercial facility
4.Telecom system
5.Medical/bank system
6.Precision instrument
Specification
Model | 3B3 10K | 3B3 15K | 3B3 20K | 3B3 30K | 3B3 40K | 3B3 60K | 3B3 80K | 3B3 100K | 3B3 120K |
Capacity | 10 KVA | 15 KVA | 20 KVA | 30 KVA | 40 KVA | 60 KVA | 80 KVA | 100 KVA | 120 KVA |
Input features | |||||||||
Input voltage(Vac) |
380±25% | ||||||||
Frequency(HZ) | 40—70Hz Automatically select synchronization range according to grid frequency | ||||||||
Bypass synchronous range (Hz) |
50/60±5%(±10% for optional) | ||||||||
Phase | 3φ4W+PE | ||||||||
Battery voltage(Vdc) |
384 | ||||||||
Battery quantity(Pcs) |
30-34 can be set
| ||||||||
Output features | |||||||||
Power factor | 0.8/0.9 | ||||||||
Voltage(Vac) | L-N:220/230/240±1% L—L:380/400/415±1% | ||||||||
100% three-phase load unbalanced voltage stability |
≤2%,allow 100% unbalanced | ||||||||
Frequency(HZ) | Mains normal,same as mains frequency;Mains abnormal,50±0.2% | ||||||||
Transfer Time(ms) |
0 | ||||||||
Efficiency(AC mode @ full loads) | ≥92% | ||||||||
Parallel function |
Yes(for optional) | ||||||||
Waveform | Linear Load THD<3%;Non-linear Load THD<5% | ||||||||
Overload capacity | 125% full load keep 10min;150% full load keep 1min; | ||||||||
Crest Factor | >3:1 | ||||||||
Others | |||||||||
Manual maintenance bypass |
with no transfer time bypass maintenance switch | ||||||||
Communication function | RS232 / RS485/dry contact | ||||||||
SNMP(optional) | Can be network monitored by SNMP adapter | ||||||||
Noise (dB) | <65(within 1 meter) | ||||||||
Alarm | Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection | ||||||||
Protection | Input over-voltage protection, battery under-voltage protection, overload protection, short circuit protection, over temperature protection | ||||||||
Cooling way | Forced cooling | ||||||||
Working Temperature(℃) |
0~40 | ||||||||
Humidity | 0~95%,No Condensing | ||||||||
EMC | GB7260.2 | ||||||||
Size(D×W×H) (mm) |
730*380*1320 | 730*555*1210 | 740*810*1410 | 745*1420*1810 | |||||
Weight(KG) | 160 | 180 | 220 | 240 | 320 | 440 | 520 | 820 | 940 |
Note:
1, Because the products are continuously improved, please contact the company or dealer to inquiry the latest specification.