10-80kVA Three Phase High Frequency Online UPS Power Supply with No Transfer Time
- Product Details
- Company Profile
1.Full DSP control technology 2.Output power factor up to 0.9,IGBT rectifier 3.Intelligent SNMP+USB+EPO (optional) 4.RS232/RS485/dry contact communication port 5.ECO fuction 6.Maintenance switch 7.DC cold start function 8.Intelligent fan speed control
3W3 10-80kVA
Main feature
1.Full DSP control technology
2.Output power factor up to 0.9,IGBT rectifier
3.Intelligent SNMP+USB+EPO (optional)
4.RS232/RS485/dry contact communication port
5.ECO fuction
6.Maintenance switch
7.DC cold start function
8.Intelligent fan speed control
Application
1.Data center
2.IT room
3.Commercial facility
4.Precision instrument
5.Telecom system
6.Rack device
Specification
Model | 3W3RX10K S/L | 3W3IX20K S/L | 3W3IX30K S/L | 3W3IX40K S/L | 3W3IX60K L | 3W3IX80KL | |||||
Capacity | 10kVA | 20kVA | 30kVA | 40kVA | 60kVA | 80kVA | |||||
Input features | |||||||||||
Input voltage(Vac) | 380(-45%~+25%),-45%~-20% | ||||||||||
Bypass voltage(V) | +15%(+20% optional)/-25% | ||||||||||
Frequency(HZ) | 40—70Hz Automatically select synchronization range according to grid frequency | ||||||||||
Phase | 3φ4W+PE | ||||||||||
Power Factor | ≥0.99 | ||||||||||
Battery voltage(Vdc) | 240 | ±192 | |||||||||
Quantity of battery(Pcs) | 16-20 can be adjusted | 28-32 can be adjusted | |||||||||
Battery type |
20*7Ah12V /External
|
32*9Ah 12V /External
|
32*12Ah 12V /External
|
32*12Ah 12V /External
|
External | ||||||
Output features | |||||||||||
Power factor | 0.9 | 0.8/0.9 | |||||||||
Voltage(V) | 380/400/415±1% | ||||||||||
Frequency(HZ) | Mains normal,Same as input;Mains abnormal,50±0.2% | ||||||||||
Transfer Time(ms) | 0 | ||||||||||
Efficiency (AC mode @ full loads) | ﹥93% | ﹥94%
| |||||||||
N+X in parallel | 3pcs | 8pcs | |||||||||
Waveform | Linear Load THD<3%;Non Linear Load THD<5% | ||||||||||
Overload capacity | 125% full load keep 10 mins,150% full load keep 60s | ||||||||||
Crest factor | >3:1 | ||||||||||
Others | |||||||||||
Manual maintenance bypass | with no transfer time bypass maintenance switch | ||||||||||
Communication | RS232/RS485/dry contact(SNMP/USB are optional) | ||||||||||
Noise (dB) | <58(within 1 meter) | ||||||||||
Alarm | Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection | ||||||||||
Protection | Input over-voltage protection, battery under voltage protection, overload protection, short circuit protection, over temperature protection | ||||||||||
Cooling way | Forced cooling | ||||||||||
Working Temperature(℃) | 0~40 | ||||||||||
Humidity | 0~95%,no condensing | ||||||||||
EMC | GB7260.2 | ||||||||||
Size(D×W×H) (mm) | 250*592*826/576 | 420*643*956 | 470*710*1150 | 600*810*1830 | |||||||
Weight(KG) | 109/38 | 183/82 | 222/110 | 226/114 | 145 | 306 |
Note:
Because the products are continuously improved, please contact the company or dealer to inquiry the latest specification.