EKL6-100 RCCB ELCB IDR Residual Current Circuit Breaker
Recommended by CCCME
- Product Details
- Company Profile
EKL6-100 RCCB ELCB IDR Residual Current Circuit Breaker
Technical Data
Technical Data
Electrical Features
Mode | Electromagnetic |
Type | AC,A,G,S |
Rated current In | 25,40,63,80,100A |
Poles | 2P(1P+N),4P(3P+N) |
Rated voltage Ue | 2P 240V~ |
4P 415V~ | |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated residual operation current(I△n) | 30,100,300mA |
Rated residual making and breaking capacity (I△m) | 630 |
Short-circuit current Inc= I△c | 6,000A/10,000A |
SCPD fuse | |
Break time under I△n | ≤0.1s |
Rated impulse withstand voltage(1.5/50) Uimp | 4000V |
Dielectric test voltage at ind.Freq. for 1min | 2.5kV |
Electrical life | 2,000 Cycles |
Mechanical life | 4,000 Cycles |
Installation
Contact position indicator | Yes |
Protection degree | IP20 |
Ambient temperature(with daily average≤35℃) | -5℃~+40℃ |
Storage temperature | -25℃~+70℃ |
Terminal connection type | Cable/Pin-type busbar |
Terminal size top/bottom for cable | 35mm2 18-2AWG |
Terminal size top/bottom for busbar | 35mm2 18-2AWG |
Tightening torque | 3.0Nm 22In-lbs |
Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
Connection | From top and bottom |
Tripping Current Range
Type | Tripping current I△/A | ||
AC | 0.5I△n<I△<I△n | ||
A | Lagging Angle | I△n>0.01A | I△n≤0.01A |
0° | 0.35I△n≤I△≤1.4I△n | 0.35I△n≤I△≤2I△n | |
90° | 0.25I△n≤I△≤1.4I△n | 0.25I△n≤I△≤2I△n | |
135° | 0.11I△n≤I△≤1.4I△n | 0.11I△n≤I△≤2I△n |
Alternative Current Sensitive | Pulsating direct current sensitive | Surge current proof |
They react to AC current which, | They react to AC and pulsating DC fault | RCCB’s surge capacity. |
Circuit Diagram
Overall and Installation Dimension(mm)