EKL9-40 1P+N RCBO circuit breaker
Recommended by CCCME
- Product Details
- Company Profile
EKL9-40 1P+N RCBO circuit breaker
Technical Data
Electrical Features
Mode | Electronic |
Type | AC,A |
Rated current In | 6,8,10,13,16,20,25,32,40A |
Poles | 1P+N |
Rated voltage Ue | 240V~ |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated residual operating current(I△n) | 10,30,100,300mA |
Break time under I△n | ≤0.1s |
Rated breaking capacity | 6,000A |
Energy limiting class | 3 |
Rated impulse withstand voltage(1.5/50) Uimp | 4,000V |
Dielectric test voltage at ind.Freq. for 1min | 2kV |
Pollution degree | 2 |
Thermo-magnetic release characteristic | B,C |
Mechanical Features
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indicator | Yes |
Protection degree | IP20 |
Reference temperature for setting of thermal element | 30℃ |
Ambient temperature (with daily average≤35℃) | -5℃~+40℃ |
Storage temperature | -25℃~+70℃ |
Installation
Terminal connection type | Cable/Pin-type busbar |
Terminal size top/bottom for cable | 16mm2 18-5AWG |
Terminal size top/bottom for busbar | 16mm2 18-5AWG |
Tightening torque | 2.5Nm 22In-lbs |
Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
Connection | From top and bottom |
Combination with accessories
Auxiliary contact | EKM2-OF |
Alarm contact | EKM2-FB |
Shunt release | EKM2-MX |
Over voltage protection | Yes |
Under voltage protection | Yes |
Over/Under voltage protection | Yes |
Tripping Current Range
Type | Tripping current I△/A | |
AC | 0.5I△n<I△<I△n | |
A | I△n>0.01A | I△n≤0.01A |
0.35I△n≤I△≤1.4I△n | 0.35I△n≤I△≤2I△n | |
0.25I△n≤I△≤1.4I△n | 0.25I△n≤I△≤2I△n | |
0.11I△n≤I△≤1.4I△n | 0.11I△n≤I△≤2I△n |