MWG1 -Remote I/O Module
- Product Details
- Company Profile
MWG1 -Remote I/O Module
MWG1 is a full isolation communication and control model with rugged construction, DIN rail mounting design, not only it support standard Modbus RTU, Modbus TCP protocols, but combine with M series vary I/O modelsto constitute many applications including: remote monitoring, distributed control, and SCADAwithstand harsh industrial environments.
Features
1-channel Temperature/mV/Ohm Input, 1 ch. Current Output
4-way isolation eliminates potential ground loops between power, Inputand network circuitry
The input signal type & measurement range can be programmed setting by ZPconfig software through USB adaptor
Hot Swappable
Low Power Loss, Low Temperature Drift, Auto Zero Calibration
Terminal Block & Rail bus redundant power
Standard Modbus RTU protocol with high-speed RS-485 communication (up to 115K bps)
Combine with MWG1 to constitute a remote I/O DAS support both of MODBUS RTU and MODBUS TCP protocols
Specification
◆ RS485 (Master) :
Protocol: Modbus RTU,ZPBUS
Support up to 31 I/O models
Data Format: 1 Start Bit. 8 Data bits.no Parity.1 Stop Bit
Analog Input Channels: MAX 60
Discrete Input Channels: MAX 60
Analog Output Channels: MAX 60
Discrete Output Channels: MAX 60
◆ RS485 (Slave)
Protocol: Modbus RTU
Address ID range: 1~254
Data Format: 1 Start Bit. 8 Data bits.no Parity.1 Stop Bit
◆ RJ45 (10BaseT/100Base TX)
Protocol: Modbus TCP, TCP/IP, http
Modbus TCP(client):6 connections
http (client) : 2 connections
◆ Power Supply:24VDC±10% or AC
◆ A/D resolution:24 bit
◆ 4-way isolation between RS485(master)/RS485(slave) /RJ45/Power Supply:≥1500VAV/1min
◆ 4-way isolation resistance:≥100Mohm/500V
◆ Operation Temperature:-10~70°C
◆ Storage Temperature:-40~85°C
◆ Relative Humidity:5-95% non-condensing
◆ EMC:EN1326: 1997+A1:1998+A2:2001+A3:2003
◆ Power Loss: 1.2 W
◆ Weight: 95g
Dimension