PAC 3200 Siemens Multifunction Meter
- Product Details
- Company Profile
PAC 3200 Siemens Multifunction Meter
The PAC3200 siemens multifunction meter is a powerful compact power monitoring device that is suitable for use in industrial, government and commercial applications where basic metering and energy monitoring is required. The meter may be used as a standalone device monitoring over 50 parameters or as part of an industrial control, building automation or global power monitoring system. Metering and monitoring applications range from simple analog volt and amp meter replacements to stand-alone sub billing or cost allocation installations with multiple tariffs.
The PAC3200 can also be used to support LEED certification and provide the needed energy metering data for federal/local government energy reduction programs. The PAC3200 provides open communications using Modbus RTU/TCP, PROFINET and PROFIBUS-DP protocols for easy integration into any local or remote monitoring system. simple configuration of the meter can be done from the front display or by using a PC with SENTRON power config setup software, supplied with the meter.
Features
Compact and powerful
More than 50 parameters can be monitored
Can be used in a variety of applications (industrial, government, commercial, etc.)
Can support LEED certification
Can be integrated into local or remote monitoring systems
Simple configuration
Application
All power parameter measurement;
Energy measurement and electrical fire monitor and control;
Replacing the three-phase power meter, three phase electricity transmitter;
Transformers, generators, capacitors and electric motors distributed detection;
Medium and low pressure systems;
SCADA, EMS, DCS integrators.
Specification
Inputs / Outputs | |
Input voltage / at digital input ? initial value for signal<1>-recognition ? at DC / rated value ? Full-scale value for signal <0> recognition | 13 V 24 V 8 V |
Number of digital outputs | 1 |
Number of digital inputs | 1 |
Digital output version | Switching or pulse output function |
Input current / at digital input ? for signal <1> | 7 mA |
? Output current ? at digital output / with signal < 0 > / maximum ? at digital output / for signal < 1 > / minimum ? at digital output / for signal < 1> / maximum ? at the digital outputs / at DC / maximum | 0.2 mA 27 mA 27 mA 100 mA
|
Output delay / at digital output ? for signal < 0 > to < 1 > / maximum ? for signal < 1> to < 0 > / maximum | 5 ms 5 ms |
Operating voltage / as output voltage / at DC / maximum permissible | 30 V |
Property of the output / Short-circuit proof | Yes |
Input delay time / at digital input ? for signal < 0 > to < 1 > / maximum ? for signal < 1> to < 0 > / maximum | 5 ms 5 ms |
Internal resistance / at the digital outputs | 55 Ω |
Measuring category / for digital signals | CATII |
Switching frequency / at digital output / maximum | 17 Hz |
Measuring inputs Outer conductors and neutral conductors internal resistance / for voltage measurement | 1.05 MΩ |
Measurable supply voltage ? between (PE)N and L / at AC / minimum ? between (PE)N and L / at AC / maximum ? between (PE)N and L / at AC / maximum rated value ? between the outer conductors / at AC / minimum ? between the outer conductors / at AC / maximum ? between the outer conductors / at AC / maximum rated value | 40 V 480 V 400 V 70 V 831 V 690 V |
Voltage measuring range extension / with external voltage transformers | Yes |
Current measuring range extension / with external current transformers | Yes |
Measuring category / for voltage measurement | CATIII |
Supply voltage / between the outer conductors / at AC / maximum permissible | 831 V |
Consumed active power / for current measurement / per phase | 115 mW |
Continuous current / at AC / maximum permissible | 10A |
Measuring category / for current measurement | CATIII |
Zero suppression / for current measurement | 0.1...10 % |
Relative measurable current / at AC ? minimum ? maximum | 1 % 120 % |
Measuring procedure / for current measurement | TRMS |
Measurable current / 1 / at AC / Rated value | 1 A |
Short-time current resistance (Icw) / limited to 1 s / rated value | 100 A |