KPM 73 Multifunction Meter with accurate measurement of power parameters, bi-directional four-quadrant energy measurement, statistics, recording functions, using advanced ARM processor and digital signal processing technology.
Features
Measure over 30 kinds of basic electricity such as phase/line voltage, three-phase current, zero sequence voltage, zero sequence current, active power, reactive power, apparent power, active energy, reactive energy, power factor, frequency
Measure and display the average power factor of the last three months and accurately grasp the amount of monthly reactive energy consumption
Class 0.5S 4 quadrant power statistics and multi-rate statistics
Demand statistics and record the maximum value, minimum value Working hours, load time statistics
Time recording function, can record 100 event
Support up to 51st harmonic calculation, total harmonic distortion rate calculation, unbalance rate, current K factor calculation
Standard 1-way Rs485 communication interface, Modbus-RTU protocol, Optional Profibus-DP Communication module.
Optional 4-way passive digital input Optional 4-way relay output
Optional 1-way 4-20mA analog output
1 road passive optical coupler collector active pulse output Optional 1-way PT100 temperature input
256 points / cycle voltage, current sampling, to ensure measurement accuracy
FSTN large screen LCD, bright LED back light uniform display, in the bright light and large viewing angle environment to obtain a good visual effect
Application
All power parameter measurement;
Energy measurement and electrical fire monitor and control;
Replacing the three-phase power meter, three phase electricity transmitter;
Transformers, generators, capacitors and electric motors distributed detection;
Medium and low pressure systems;
SCADA, EMS, DCS integrators.
Specification
Working power source | Operating Voltage | AC 85-270V/DC 80-300V |
Rated power consumption | < 3VA | |
Input voltage | Rated voltage | 57.7/100V,220/380V,380V/660V Need to customize |
Sill value | 5V | |
Overload capacity | 1.2 times rated voltage allowed, continuous work; 2 times the rated voltage allowed 1second | |
Power consumption | <0.5VA/phase(rated) | |
Measurement range | Phase voltage(LN):50~270VAC, line voltage(LL):90~470VAC | |
Input current | Frequency range | 45~65Hz |
Rated current | Default 5A,Input range 1-6A;Optional 1A,Input range 1-1.2A | |
Sill value | 5A Configuration,5mA ;1A Configuration,0.8mA | |
Overload capacity | 1.2 times rated current allowed, continuous work; 20 times the rated current allowed 1 second | |
Power consumption | <0.75VA/phase(Rated current 5A);<0.25VA/phase(Rated current 1A) | |
Input output | Switch value input | 4-way passive main line contact DI input, internal supply DC24V power source |
Relay output | 4-way DO output, Contact capacity 250VAC/5A,30VDC/5A | |
Analog output | Output range 4~20mA,overload allows 1.2times | |
Temperature input | Measure range 0℃~100℃ | |
Power quality monitor | Harmonic measurement | Voltage/current 2~51st harmonic distortion rate total harmonic distortion rate. |
Harmonic distortion rate | Phase voltage, line voltage | |
Imbalance rate | Voltage. current | |
Measurement accuracy | Voltage | ±0.2%(0.01V) |
Current | ±0.2%(0.01A) | |
Active power | ±0.5%(0.1W) | |
Reactive power | ±2.0%(0.1kvar) | |
Active energy | ±0.5%(0.1kWh) | |
Reactive energy | ±2.0%(0.1kvarh) | |
Power factor | ±0.5%(0.001) | |
Frequency | ±0.02Hz(0.01Hz) | |
Temperature | ±1℃(1℃) | |
Communication | Communication interface | RS485,Profibus-V1,Photoelectric isolation interface |
Communication protocol | ModbusRTU,1200~38400bps; Probibus-DP,9600~12Mbps | |
Electrical insulation | Power frequency withstand voltage | AC2kV/min~1mA Input-output-power source |
Insulation resistance | >50MΩ | |
Impact voltage | 5kV Peak ,1.2/50us | |
Working environment | Operating temperature | -25℃ ~ +70℃ |
Relative humidity | 5%~95% No condensation | |
Storage temperature | -30℃ ~ +75℃ | |
Altitude | No more than 4000m | |
Electromagnetic Compatibility | Surge (impact) immunity | IEC61000-4-5,Level4 |
Electrical fast burst immunity | IEC61000-4-4,Level4 | |
Electrostatic discharge immunity | IEC61000-4-2,Level4 | |
Power frequency magnetic field immunity | IEC61000-4-8,Level4 |