QPV Frequency Transducer converts an ac / dc voltage or current input into a load independent output signal. It has excellent temperature characteristic and good working stability. The output signal is based on the root mean square(RMS) measurement of the input signal and hence the transducer can be used with distorted waveforms. The unit conforms to IEC 60688. In addition, it meets the insulation requirements of IEC 60255-5, clauses 5, 6 and 8 as well as the high frequency disturbance test of IEC 60255-22 for Class III test voltage.

Compared with the past transducers, the QPV power transducer, made of new technologies and materials, have been greatly improved in circuit, process, structure, etc., making its measurement accuracy higher and work more stable.

 



Features

  • Accuracy 0.5 class

  • 85~265VAC wide voltage AUX for most country

  • With 4 channel output (support max 22 types parameter for analog output)

  • Front panel with 4 keypads for analog parameter configuration, do not need extra configuration software.

  • With RS-485 port for remote electrical data

  • 500ms response time

  • 35mm Din rail mounting

  • Advanced electrical parameter ready optional

  • SOE function optional

 

Application

  • Instrumentation panels

  • Control systems

  • Electrical distribution panels

  • Transmission systems and generators

  • SCADA systems

 

Specification

Signal Inputs
Input rating0-100V, 0-220V, 0-380V
Overload1.2 times rated continuous;
5sec @ 10 times of rated current
1sec @ 2 times of rated voltage
Burden0.5VA
Measurement Output
Standard outputs4~20mA or 0~5V
(others on request)0~20mA;

5~10V;

0~10V;
Ripple<0.5% peak to peak
Load ResistanceCurrent output: 0<Lr<510Ω;
Voltage output: Lr>10KΩ
Measurement Accuracy
Reference IEC 606880.5% or 0.2% @ F.S.
AdjustmentPotentiometer "ZERO” and "SPAN"
"T" types no need extra adjustment
Frequency influence<0.02% per Hz
Load influence<0.25% of F.S. for specific load range
Auxiliary Supply
Rating85-265Vac/dc,
Optional 12V, 24V, 48VDC
Consumption<3VA
Galvanic isolation between I/O and AUX
Test voltage2KV RMS 50Hz for 1 minute
impulse4KV 1.2/50μsec waveform
Temperature requirements
Operating-10~55C
Storage-40~70C, 20 ~ 93%RH; Noncondensing