QPPX AC Power Transducer
- Product Details
- Company Profile
QPPX AC Power Transducer
AC power transducer measures a wide range of electrical parameters and generates analog or digital output signals suitable for interfacing with instrumentation and control systems. Total four-channel output, with panel key or PC control programmable, user can free to set 4 different data from max 26 electrical parameters for sampling and analog signal output.
QPPX programmable transducer has three channel digital inputs and RS485-Modbus communication functionality. Moreover, the product can monitor the galvanically isolated DI signal and programmed the transducer with customized SCADA software. Any of the measured parameters can be read out via the RS485 connection.
Features
Accuracy 0.5 class
85~265VAC wide voltage AUX for most country
With 4 channel output (support max 22 types parameter for analog output)
Front panel with 4 keypads for analog parameter configuration, do not need extra configuration software.
With RS-485 port for remote electrical data
500ms response time
35mm Din rail mounting
Advanced electrical parameter ready optional
SOE function optional
Application
Instrumentation panels
Control systems
Electrical distribution panels
Transmission systems and generators
SCADA systems
Specification
Electrical Signal Inputs | |
Nominal input | 1 or 5 Amp C.T. connected |
110V, 230V, 240V, 400V, 415V ac +/-20% | |
Power consumption | <1 VA voltage |
<0.2 VA current | |
Overload capacity | 1.2 times continuous |
5sec @ 10 times of rated current 2sec @ 2 times of rated voltage | |
Frequency range | 40~65Hz |
Measurement Output | |
Standard outputs | 4~20mA/ 0-20mA programmable (0~5V / 0~10V optional) |
Maximum load | <390 Ω (current output) >10KΩ (voltage output) |
Ripple | <1% peak to peak |
Response time | <350ms 0-90% |
<500ms 0-99% | |
Measurement Accuracy | |
Class | 0.2% / 0.5 complying with IEC 60688 |
Accurate range | 0 - 120% I |
Frequency influence | <0.05% per Hz |
Load influence | <0.25% of F.S. for specific load range |
Auxiliary Supply | |
Rating | 85-265Vac/dc, Optional 12V, 24V, 48VDC |
Consumption | <3VA |
Galvanic isolation between I/O and AUX | |
Test voltage | 2KV RMS 50Hz for 1 minute |
impulse | 4KV 1.2/50μsec waveform |
Temperature requirements | |
Operating | -10~55℃ |
Storage | -40~70℃, 20 ~ 93%RH ; Noncondensing |