DPA Power Transducer
- Product Details
- Company Profile
DPA Power Transducer
DPA Power Transducer converts an ac / dc voltage or current input into a load independent output signal. It has excellent temperature characteristic and good working stability. The output signal is based on the root mean square(RMS) measurement of the input signal and hence the transducer can be used with distorted waveforms. The unit conforms to IEC 60688. In addition, it meets the insulation requirements of IEC 60255-5, clauses 5, 6 and 8 as well as the high frequency disturbance test of IEC 60255-22 for Class III test voltage.
Compared with the past transducers, the DPA power transducer, made of new technologies and materials, have been greatly improved in circuit, process, structure, etc., making its measurement accuracy higher and work more stable.
Features
2/0.5 measurement accuracy
Support customized parameters
RMS measurement and output
500ms response time
35mm Din rail mounting
High load capacity and reliability
Low ripple output
A wide range of both D.C. current and voltage inputs are offered.
Application
Used in the medium and low voltage systems.
Metering of distribution feeders, transformers, generators, capacitor banks and motors.
Measuring converter: optional association of an instantaneous parameter to one of the analogue outputs available (0...20 mA /4...20 mA)
Typically, the DPA transducer can be used to prevent earth loops, which occurs when a measuring source, that is earthed, is connected to a computer or data logger that is also earthed.
Motor control/ panel power monitoring/ power consumption monitor and control/ power distribution system/ intelligent building & automation power management system/ power testing equipment
Specification
Signal Inputs | |
Input rating | DPA 4-20mA, 0-20mA |
Overload | 1.2 times rated continuous; 5sec @ 10 times of rated current 1sec @ 2 times of rated voltage |
Burden | 0.5VA |
Measurement Output | |
Standard outputs | 4~20mA or 0~5V |
(others on request) | 0~20mA; |
5~10V; | |
0~10V; | |
Ripple | <0.5% peak to peak |
Load Resistance | Current output: 0<Lr<510Ω; |
Voltage output: Lr>10KΩ | |
Measurement Accuracy | |
Reference IEC 60688 | 0.5% or 0.2% @ F.S. |
Adjustment | Potentiometer "ZERO” and "SPAN" |
Frequency influence | <0.02% per Hz |
Load influence | <0.25% of F.S. for specific load range |
Auxiliary Supply | |
Rating | 85-265Vac/dc, Optional 12V, 24V, 48VDC |
Consumption | <3VA |
Galvanic isolation between I/O and AUX | |
Test voltage | 2KV RMS 50Hz for 1 minute |
impulse | 4KV 1.2/50μsec waveform |
Temperature requirements | |
Operating | -10~55℃ |
Storage | -40~70℃, 20 ~ 93%RH;Noncondensing |