HVD-S-2 AC/DC110V/220V Device Detector Live Line With High Voltage Capacitive Indicator
- Product Details
- Company Profile
HVD-S-2 AC/DC110V/220V Device Detector Live Line With High Voltage Capacitive Indicator
Description
The high-voltage live display device is a new type of non-contact high-voltage live detection device. It uses an integrated three-phase continuous display to test the voltage loss in the medium-voltage switchgear, which helps to ensure the safety of the power system. The device is not directly connected to the high-voltage live body Connection, can sense the electric field signal, accurately reflect the charging situation of the high-voltage electrified body, and has a reliable locking function.
The product meets the requirements of IEC 61243-5 and IEC 62271-213 standards, and is the first choice for indoor high-voltage electrical equipment to prevent accidental entry into live spaces and electrical misoperation. The device has the functions of flashing display, sound alarm, self-check, reset and start-up forced locking circuit. Cooperating with electromagnetic locks and microcomputer anti-misoperation locking functions, it is widely used in 7.2kV~40.5kV indoor and outdoor electrical equipment or networks. It is installed on line grounding switches, busbar grounding switches and busbar voltage change grounding switches to prevent The function of the charged grounding switch by mistake.
Features
l Fail-safe voltage testing and protection
l Integrated self-test function, with self-test button
l High voltage alarm, disconnection alarm
l Visual indication via bright LED or LCD screen
l No battery or auxiliary voltage maintenance-free
l Fully self-monitoring
l Three-phase live voltage indication system
l Electromagnetic lock automatic locking
l Relay signal output interlocking indication
l Phase sequence detection point.
Application
l Indicate the status of live electricity
l Ensuring the safety of the power system and the safety of personnel
l Prevent the staff from operating with electricity and causing safety accidents.
l Capable of locking high-voltage electrical equipment and
l Forcibly locking the door of switchgear
l Reflect status of high-voltage lines or high-voltage equipment
Specification
Rated voltage: | 24V/110V/220V |
Voltage level | 1..52 kV (Medium-voltage) |
Contact capacity (Passive) | 8A、250VAC/48VDC |
Power consumption | <2W |
Working frequency | 50Hz/60Hz |
Standard | IEC 61243-5 IEC 62271-213 |
Insulation strength | 2kV,1min |
Nominal Voltage | 3-3.6kV |
6-7.2kV | |
10-12kV | |
20-24kV | |
35-40.5kV | |
Shielded Cable Length | 2M,or customized by buyers |
Threshold Values for Voltage Presence Indication | U>0.40 x Unmin |
Threshold Values for Voltage Absence indication | U<0.15 x Unmin |
Threshold Values for Over-voltage Protection | U<0.30 x Unmin |
Front display | LCD/LED Display |
Controls | Self-test button |
Operating temperature | -25°C ... 55°C, RH<95%, Altitude: ≤1000m |
Storage temperature | -30°C ... 75°C, RH<95% |
Protection class | IP40/IP65 |
Type of interface | LRM |
Lifetime | Minimum 31 years (MTBF) |
Mounting Dimension (WxHxD) | Panel window size 92x45mm Recommended depth 130mm |
Working Description
Number | Name | Status | Direction |
1 | Charged Indicator Light | Bright | This Phase Is Charged |
Dark | This Phase Is Not Charged | ||
Flashing | Sensor Offline Alarm | ||
2 | Power supply Indicator | Bright | Normal Working Condition |
Dark | Non-Normal Working Condition | ||
3 | Locking Indicator | Bright | Device Locked |
Dark | Device Unlocked | ||
4 | Self-Test Button | Press | Start System Self-Test |