MCM2403 3P3W Kwh 1 Iot Electricity Electric Single Phase Smart Design Energy Meter
- Product Details
- Company Profile
MCM2403 3P3W Kwh 1 Iot Electricity Electric Single Phase Smart Design Energy Meter
Description
MCM series multi-channels power meter is a metering device specially designed for feeder loops. The design of multi-function provides electrical parameter measurement for three-phase or single phase branch circuits. Furthermore, MCM series perform real-time metering, measure energy consumption and monitor power quality. There are advanced communication options, including Modbus via RS485, optional Ethernet. Multiple digital input ports can collect pulse signal from water meters and gas meters etc.; and relay output port can remotely control field devices from host server system.
MCM 2403 is used for 4 channels 3P3W/3P4W three phase branch circuit electrical parameter collection. This product is installed with standard din-rail and is 6 models (1 model is 17.5mm) in width. In addition, with 1.6'' dot matrix LCD interface, MCM2403 can easily display all parameters on the screen.
Because of its 0.5 class high-precision performance, the product can replace multiple digital energy meters. Moreover, MCM 2403 can reduce equipment investment in electrical metering projects, improve equipment reliability and reduce maintenance costs.
Features
l 4 channels three phase circuit metering
l Accuracy: class 0.5
l Current measuring 100mA or 333mV
l 1.6'’ dot matrix LCD screen
l Universal series power supply (85-265VAC/DC)
l Provide 5 virtual alarm trigger
l With RS-485 Modbus/RTU Communications
l With harmonic analysis
l With SPDT relay output for alarm output
l Accept customization design
Application
l Metering of distribution feeders, transformers, generators, capacitor banks and motors.
l Medium and low voltage systems.
l Remote data reading.
l Alarm station with voltage-free digital inputs.
l Commercial, industrial, utility field
l Power quality analysis.
l Harmonic measurement.
Specification
Current measurement on inputs (TRMS) | |
CT secondary rated | 100mA, 333mV optional |
Measurement range | 0 ... 9999A |
Overload | 1.2 times rated continuous; |
Input consumption | <0.2 VA |
Voltage measurement (TRMS) | |
Direct measurement | 18 ... 400 VAC L-L |
PT secondary | 100VAC / 400VAC |
Frequency | 45 ... 65 Hz |
Overload | 1 seconds for 2 times the rated |
Input consumption | <0.2 VA |
Auxiliary power supply | |
AC voltage | DC/AC 85~265 ± 10 %, 50 / 60 Hz |
Consumption | < 10 VA |
I/O port (alarms / control) | |
Number of relays | 1 x SPDT relay |
Type | 230 VAC 5 A, passive node |
Communication | |
Link | RS485 (2/3 wires half duplex) |
Protocol | Modbus RTU mode |
MODBUS speed | 4800/9600/12800/19200bps |