TREF1 63A 2 Poles, Earth Leakage Protection, Moulded Case Circuit Breaker Type ELCB
- Product Details
- Company Profile
TRE series circuit breaker and auxiliaries comply with the following international standard: 1.IEC/EN 60947-1 Low-voltage switchgear and controlgear-part 1: General rules; 2.IEC/EN 60947-2 Low-voltage switchgear and controlgear-part 2: Circuit breakers; TRE series ELCB(Standard use environment for TRE series ELCB) 1. Ambient temperature: Within the range of -5oC--+40oC(However, the average for the duration of 24 hours must not exceed 35oC); 2. Altitude: 2000m or less 3. Installation class: III 4. The magnetic field near the instalation site should not be more than five times the earth magnetic field in any direction. 5. Pollution: II Classification: According to the poles: 2-poles, 3-poles According to the breaking capacity: S-type, H-type According to the rated current: Fix type, Adjustable type(08In-1.0In) According to the trip action time: Fix type, Adjustable type(0.1s/0.3s/0.5s or 0.45s/1.0s/2.0s) According to the rated residual current: Fix type, Adjustable(30mA/100mA/300mA/500mA)
TRE series ELCB
Standard:
TRE series circuit breaker and auxiliaries comply with the following international standard:
1.IEC/EN 60947-1
Low-voltage switchgear and controlgear-part 1: General rules;
2.IEC/EN 60947-2
Low-voltage switchgear and controlgear-part 2: Circuit breakers;
TRE series ELCB(Standard use environment for TRE series ELCB)
1. Ambient temperature: Within the range of -5oC--+40oC(However, the average for the duration of 24 hours must not exceed 35oC);
2. Altitude: 2000m or less
3. Installation class: III
4. The magnetic field near the instalation site should not be more than five times the earth magnetic field in any direction.
5. Pollution: II
Classification:
According to the poles: 2-poles, 3-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)
According to the trip action time: Fix type, Adjustable type(0.1s/0.3s/0.5s or 0.45s/1.0s/2.0s)
According to the rated residual current: Fix type, Adjustable(30mA/100mA/300mA/500mA)
Technical data table:
Ampere frame size | TREF1(63A) | ||||
Breaking capacity code | S | H | |||
Product code and poles | 2P | 3P | 2P | 3P | |
TREF1-S2 | TREF1-S3 | TREF1-H2 | TREF1-H3 | ||
Protective function | Over load & Short circuit & Ground fault | ||||
Rated current, In(A) | 15, 20, 30, 40, 50, 63 | ||||
Rated residual current | Operating, IΔn(mA) | 30, 50, 100, 200, 300, 500 | |||
Non-operating, IΔno(mA) | 15, 25, 50, 100, 150, 250 | ||||
Adjustable part | Rated current setting(0.8In-1.0In) | √ | √ | √ | √ |
Lockup device for operating handle | χ | √ | χ | √ | |
Residual current, IΔn | 30mA/100mA/300mA/500mA | ||||
Trip action time | 0.1s/0.3s/0.5s | ||||
Rated operational voltage, Ue(V), AC 50/60 Hz | 240/415 | ||||
Rated insulation voltage, Ui(V) | 1000 | ||||
Rated impulse withstand voltage, Uimp(kV) | 8 | ||||
Residual current off-time at IΔn ,Sec (s) | 0.1 | ||||
Standard | Conformity with IEC/EN 60947-2 | ||||
Rated frequency(Hz) | 50/60 | ||||
Rated short-circuit breaking capacity, Icu(kA) | |||||
AC | 240V | 14 | 25 | ||
415V | 5 | 7.5 | |||
Ics=% * Icu | 100% | ||||
Mechanical life(circle) | 8500 | ||||
Electrical life(circle) | 1500 | ||||
Dimension: Length*Width*Height | 2-poles | 100*50*60 | |||
3-poles | 100*75*60 | ||||
4-poles | - |
Built-in accessory:
Built-out accessory:
Company show:
Exhibition: