DTZY217(T12-1)Three Phase Smart Meter with Communication as per DL/T645-2007 with KEMA cer
- Product Details
- Company Profile
DZY217(12-1)Three Phase Smart Meter with communication as per DL/T645-2007 can measure import and export active energy, inductive and capacitive reactive energy with TOU and step tariff functions, and can be optional with PLC or RF module. It can be controlled to disconnect and reconnect the load remotely.
General introduction:
DZY217(12-1)Three Phase Smart Meter with communication as per DL/T645-2007 can measure import and export active energy, inductive and capacitive reactive energy with TOU and step tariff functions, and can be optional with PLC or RF module. It can be controlled to disconnect and reconnect the load remotely.
Main functions:
1. Data snapshot : It supports freezing which include daily freezing , hourly freezing , occasional freezing , immediate freezing
2. Event logs : It can separately record latest 10 times events , such as power outage , programming , time correction , meter cover open and terminal cover open , disconnection and re-connection , reset of events , reset of meter, etc
3. Communication interface : The meter has one infrared interface, one RS485 and one PLC or GPRS module interface. Interfaces are independent . The protocol of meter conforms to DL / T645-2007 .
Technical specifications:
Items Contents
Standards IEC62052-11;IEC62053-21:IEC62053-22;EC62053-23
Accuracy Active: Class 0. 2S. 0.5S or Class 1 Reactive: Class 2
Protocol DL/T 645-2007
Reference voltage 3x57.7/100V; 3x120/208V;3x220/380
Current CT connection: 1.5(6)A, 5(6)A,5(10)A,Direct connection :10(40)A,10(60)A,20(80)A,10(100)A
Reference frequency 50/60Hz
Power consumption <1.5W, 6VA(per phase)
Operation voltage range 0.8Un~1.2Un
Limited operation voltage range 0.7Un~1.3Un
Operation temperature -25℃~+60℃
Limited operation temperature -40℃+70℃
RTC deviation ≤0.5s/d
Life time 15 years
Size 290mm(L)x170mm(W)x85mm(H)
Net weight About 2.8kg