Industrial Commercial Medical Filter Air Handling unit Ahu Clean Room Air Conditioner
Industrial Commercial Medical Filter Air Handling unit Ahu Clean Room Air Conditioner
Industrial Commercial Medical Filter Air Handling unit Ahu Clean Room Air Conditioner
Industrial Commercial Medical Filter Air Handling unit Ahu Clean Room Air Conditioner

Industrial Commercial Medical Filter Air Handling unit Ahu Clean Room Air Conditioner

Manufacturer,Engineering Contracting Company

  • Product Details
  • Company Profile

An air handler, or air handling unit (often abbreviated to AHU), is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, heating or cooling elements, filter racks or chambers, sound attenuates, and dampers

Product NameIndustrial commercial air unit central air conditioner
Lifetime>20 years
ConditionNew
Optional functionCooling/Heating/Air Filtering/Dehumidification etc
Transport packagePlywood case
MountingCeiling, floor standing
Operating voltage380/400 VAC
CertificationRoHS, ISO, CE, CCC
OriginChina
ApplicationClean room, industrial, hospital, medical
HS code8415101000

>>Performance and Quality Standard:


Model

TFNP(14)ADA

TFNP(16)ADA

TFNP(21.5)ADA

TFNP(24.8)ADA

Cooling Capacity

kW

14

16

21.5

24.8

Heating Capacity

kW

15.5

17

26.3

29

Power Supply

V/Ph/Hz

380-415/3/50

Compressor

Type

Rotary Type

Scroll Type

Quantities

Pieces

1

1

2

2

Power Input

Cooling

kW

3.9

4.53

8.2

9.03

Heating

kW

4.25

4.85

8.7

9.23

Refrigerant

Type


R410A

Weight

kg

2.9

3.2

5.5

7

Condenser (Air Side)

Air Side Heat-Exchanger Type

Copper-Fin-Coil

Quantities of Fan Motor

Pieces

1

Air Flow Volume

×103m3/h

7

7

9

10

Fan Motor Input

kW

0.2

0.2

0.7

0.7

Evaporator (Water Side)

Water Side Heat-Exchanger Type

Plate Type

Water Resistance Loss

kPa

18

19

38

39

Water Inlet/Outlet Pipeline Diameter

mm

DN40

Water Flow Volume

m3/h

2.15

2.49

3.7

4.3

Max. Pressure

MPa

1

Water Pipe Connection Type

Soft Connection

Dimension

L

mm

970

970

1600

1600

W

mm

400

400

900

900

H

mm

1327

1327

1080

1080

Packing Size

L×W×H

mm

1082x435x1456

1082x435x1456

1620x1034x2041

1620x1034x2041

Weight

Net Weight

kg

111

120

270

290

Operating Weight

kg

112

122

300

330

Connection Wiring

Power Wiring

mm2×No.

10×5-Core

Signal Wiring

mm2×No.

0.75×3-Core

Control Type

Wired Controller

Safety Protection Device

High/low-pressure switch, anti-frost  protection, water-flow switch, over-load  protection, and power phases sequence protection.

Electric Heater

Power Supply

V/Ph/Hz

380/3/50

(Optional)

Power Input

W

7.5

15

7.5

15

Noise Level

dB(A)

61

60

61

60

Operation Water Temp

°C

Cooling:5~17  Heating:45~50

Ambient Temp

°C

Cooling:5~17  Heating:45~50


Send Inquiry to This Supplier

  • Title
  • From*
  • to
  • Message*
  • Minimum Order Quantity*
  • Unit
  • Verification Code*