KEYPOWER GENERATOR TESTER SPECIFICATIONS | ||||
Measurement | Range | Accuracy | Resolution | Overload |
Voltage (V) | 10.0~500.0V | ± (0.4% reading+0.1%range) | 0.1V | 600V |
Current (A) | 0.030~5.000A | ± (0.4% reading+0.1%range) | 0.001A | 6A |
Power | According to volt range & current range | Power factor =1.0 | <200W 0.1W | |
± (0.4% reading+0.1% range) | ≥200W 1W | |||
Power factor =0.5 | ≥2kW 10W | |||
± (0.8% reading+0.2% range) | ||||
Power Factor | 0.20~1.00 | ±0.02 | 0.001 | |
Frequency | 45~65Hz | ±0.2Hz | 0.01Hz | |
Running Time | 99h59m | ±2min/hour | 1 minute | |
Energy (kWh) | 99999kWh | Power factor= 1.0 | 0.001kwh | |
± (0.4% reading+0.1% range) | ||||
Power factor=0.5 | ||||
± (0.8% reading+0.2% range) | ||||
Harmonic Analysis (%) | 2-50 times and total harmonic |
Models You Can Choose | |||||||||
Model | Testing capacity | Type of load | Duty | Cooling system | Phase | Rated Testing Voltage | Rated Frequency | Dimensions (L*W*H) (mm) | Weight (kg) |
KPLB-100 | 0 - 100 kw | Resistive or Reactive, PF = 1.0 or 0.8 | Continuous | Industrial grade axial fan | Available at both single and three phase | 110-480 VAC | 50/60 Hz | 960*1060*1400 | 350 |
KPLB-200 | 0 - 200 kw | 1560*1310*1650 | 850 | ||||||
KPLB-300 | 0 - 300 kw | 1690*1440*1750 | 1100 | ||||||
KPLB-400 | 0 - 400 kw | 1900*1600*1900 | 1250 | ||||||
KPLB-500 | 0 - 500 kw | 1900*1600*1900 | 1400 | ||||||
KPLB-600 | 0 - 600 kw | 2100*1730*2000 | 1550 | ||||||
KPLB-700 | 0 - 700 kw | 2100*1730*2000 | 1650 | ||||||
KPLB-800 | 0 - 800 kw | 2400*2030*2100 | 2010 | ||||||
KPLB-1000 | 0 - 1000 kw | 2400*2030*2100 | 2250 | ||||||
KPLB-1300 | 0 - 1300 kw | 3500*2270*2150 | 3070 | ||||||
KPLB-1400 | 0 - 1400 kw | 3500*2270*2150 | 3150 | ||||||
KPLB-1500 | 0 - 1500 kw | 3500*2270*2150 | 3300 | ||||||
KPLB-1600 | 0 - 1600 kw | 6058*2438*2591 | 6000 | ||||||
KPLB-2000 | 0 - 2000 kw | 6058*2438*2591 | 7360 | ||||||
KPLB-2200 | 0 - 2200 kw | 6058*2438*2591 | 7700 | ||||||
KPLB-2500 | 0 - 2500 kw | 6058*2438*2591 | 8100 |
Specifications
100-2000KW Load Bank for Generator Load Test:
1.Premium components
2.Durable and reliable
3.Easy to transport
Load bank is a simulating load test equipment used for generators,
UPS, battery banks etc power systems load test.
1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade magnesium oxide.
2. Rated testing voltage: AC 3P4W, 110-480V 50/60 Hz.
3. Cooling mode: Forced air-cooled, fans mounted on the side of the load bank blow horizontally. Testing power or external utility power supply for fans.
4. Working mode: Load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.
5. Load bank features world-famous components to ensure reliable performance and longer service life including:
SCHNEIDER contactors.
Siemens switches, knobs and indicators.
ABB Circuit breakers.
OMRON intermediate relays.
PHOENIX terminal blocks.
6. Parameter measuring accuracy grade: 0.3
7. Load control accuracy: ± 5%.
8. Load bank protections: Over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: Two control modes available:
A)Local manual control;
B)Optional: Manual control via a remote control panel (max control distance is 30m).
10. Parameter display and measurement:
Control panel contains a LOVATO Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc.
(Optional: A professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing). "
11. Operating environment:
Altitude: ≤ 3000m above sea level. Ambient temp: -10~+50 ℃
Relative humidity: ≤ 80% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.
Any question, please contact me directly.
Related Products >>>>>>>>
Fuzhou GFF KEYPOWER Equipment Co., Ltd is a dedicated manufacturer with more than a decade's experience in manufacturing and developing generator set and load bank.KEYPOWER is located in the coastal city of Fuzhou which lies to the west of Taiwan strait, with factory address at No. 1, Gaoqi Industrial Park, Nanyu town, Minhou county, Fuzhou, the park covers an area of 66,000 square meters including diesel generator assembling workshop of more than 8,000 square meters. With a professional team consisting of 150 qualified staff members as well as state-of-the-art processing equipments and innovative design philosophy,KEYPOWER manufactures and sells 3000-5000 units of high quality generator sets and load banks every year.