CQB7R-125 10kA Miniature Circuit Breaker Reclosing
- Product Details
- Company Profile
CQB7R-125 Reclosing MCB is used to combine with Prepaid Meter, when the electricity user prepaid is used up, the MCB will break automatically when getting a signal from the Prepaid Meter. It can be switched on automatically when the Prepaid Meter get a signal that user have bought the electricity.
1 Application
CQB7R-125 Reclosing MCB is used to combine with Prepaid Meter, when the electricity user prepaid is used up, the MCB will break automatically when getting a signal from the Prepaid Meter. It can be switched on automatically when the Prepaid Meter get a signal that user have bought the electricity.
2 Type designation
3 Technical data
Specifications | |
Rated voltage | 230V~(1P+N,2P)、400V~(3P,3P+N,4P) |
Rated impulse withstand voltage Uimp | 6000V |
Rated current(A) | 40、50、63、80、100、125 |
Rated frequency | 50Hz / 60Hz |
Number of poles | 1P+N、2P、3P、3P+N、4P |
Rated breaking capacity lcn(A) | 6kA, 10kA(High breaking type) |
Short-circuit capacity Ics(A) | 6kA, 7 .5kA(High breaking type) |
Mechanical life(cycles) | ≥10000 |
Electrical life(cycles) | ≥6000 |
Overvoltage category | Ⅲ |
Torque | 2.5N·M |
Automatic closing time | t ≤ 3s |
Automatic switch-off time | t≤ 2s |
Signal Connection Wire Length | 300mm (Customizable on demand) |
Tripping characteristics | See Table 1 |
Pollution degree | 2 |
Standard | IEC60898-1、GB10963.1 |
Compliant certification | CCC |
Table 1 Tripping characteristics(Reference temperature 30℃)
Item | Curves | Test current ln(A) | Status | Time limit for tripping or non-tripping | Expected result | Remarks |
a | B、C、D | 1.13ln | Cold | t≤1h(In≤63A) t≤2h(In>63A) | Non-tripping | Current smoothly rises to specified value within 5s |
b | B、C、D | 1.45ln | Following item a test | t<1h(In≤63A) t<2h(In>63A) | Tripping | |
c | B、C、D | 2.55ln | Cold | 1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) | Tripping | |
d | B C D | 3ln 5ln 10ln | Cold | t≤0.1s | Non-tripping | Switch on the power supply by closing the auxiliary switch |
e | B C D | 5ln 10ln 20ln | Cold | t<0.1s | Tripping | Switch on the power supply by closing the auxiliary switch |
Note: The term "cold " means that the test is carried out at a reference calibration temperature without load before the test.
4 Nominal operation conditions
4.1 : Ambient temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
4.2 : Altitude:≤ 2000m;
4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
4.4 : Mounting type : Din rail embedded(TH35-7.5)
4.5 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle , the installation place should be no significant impact and vibration.
4.6 Installation should be free from obvious shock and vibration.
5 Conductor requirements and cross-sectional area
Nominal cross-sectional area (mm2) | Rated current In(A) |
10 | 32<In≤50 |
16 | 50<In≤63 |
25 | 63<In≤80 |
35 | 80<In≤100 |
50 | 100<In≤125 |
6 Dimensions (unit :mm)
7 Tripping curve
8.CCC